云端儲存中心空調(diào)解決方案

 機(jī)房專用空調(diào)    |      2016-04-06
針對云端儲存中心的空調(diào)解決方案,云端儲存中心的特點(diǎn)為數(shù)字?jǐn)?shù)據(jù)存儲場所,云端儲存中心有大量發(fā)熱設(shè)備,云端儲存中心內(nèi)人員不會太多。根據(jù)云端儲存中心的特點(diǎn),空調(diào)選型推薦如下:HIMOD Q25U機(jī)型。
This is a solution of A/C for a cloud storage center. The characteristic of the cloud storage center is the storage place for digital data, and there is a large amount of equipment. Personnel are not too much. According to the characteristics of the space for the cloud storage center, the selection of model is recommended as HIMOD Q25U.
經(jīng)濟(jì)效益評估:(Economic Evaluation)
  • 該云端儲存中心需安裝空調(diào)面積總計(jì)500平方米左右,有大量發(fā)熱設(shè)備,對溫濕控制及節(jié)能有較高的要求,依據(jù)實(shí)際情況每平米所需制冷量平均按500W計(jì)算,總需求250KW制冷量。
The total area is of about 500 square meters for the cloud storage center, and there is a large amount of heat source, and it highly requires the temperature and humidity control and energy saving features. Required cooling capacity per square meter on average calculated based on the actual situation according to 500W, the total demand for cooling capacity is of 250KW.
  • 要滿足該項(xiàng)目250KW的制冷量,需使用HIMOD Q25U機(jī)組3套裝機(jī)。
To meet the cooling capacity of 250KW, this project is needed to use three sets of units (HIMOD Q25U).
  • 經(jīng)濟(jì)效益對比估算:傳統(tǒng)空調(diào)滿足250KW制冷量的輸入功率至少為101.5KW左右,而HIMOD Q25U機(jī)組1套主機(jī)的輸入功率合計(jì)為22.33KW,主機(jī)部分省電34%,全年共計(jì)節(jié)省電費(fèi)6.6萬元以上。(按1年運(yùn)行8個月,1月運(yùn)行30天,1天運(yùn)行8小時,用電按1元1度計(jì)算)
Comparison of economic benefit estimation: the traditional air-conditioning input power (250KW cooling capacity) is at least about 101.5KW, and the HIMOD Q25U input power per set is of 22.33KW. The energy saving is up to 34%. The annual saving is more than 66000 CNY. (According to 8 months per year, 30 days per month, 8 hours per day of operation, electricity by 1 CNY/1 degree calculation)